Recalls / 2002-08-09
CPSC, Square D Company Announce Recall of Circuit Breakers
02556 · Recalled 2002-08-09 · CPSC page

Description
This recall involves MA/MH circuit breakers manufactured between October 2000 and March 2002.
Hazards
The circuit breakers may have an incorrect torque load applied to the lug mounting screws. This could cause the clamping load between the lug and the circuit breaker terminals to be lower than specified, resulting in a high temperature condition. Products could overheat causing a fire hazard.
Reported injuries
None reported.
Remedy
Contact Square D for a free repair. Repairs will consist of verifying proper screw torque and tightening all screws that do not meet the required torque specifications.
Products
| Name | Model | Units |
|---|---|---|
| MA/MH circuit breakers | About 40,000 |
Parties
- Manufacturer
- Square D Company
- Made in
- United States
- Sold at
- The circuit breakers were sold, March 2002 for, 000, 000.
Consumer contact
For more information, call (800) 634-8730 between 8 a.m. and 4 p.m. PT Monday through Friday.