CPSC Recalls

Recalls / 2003-10-30

CPSC, Fire Control Instruments Announce Recall for Audio Evacuation Units

04507 · Recalled 2003-10-30 · CPSC page

Recalled Audio Evacuation Unit
Recalled Audio Evacuation Unit

Description

All FCI AEUs (part number 1100-1171) manufactured prior to April 12, 2003. These AEUs are used in FireVac 7200 System Control Units. A label in the left center of the circuit board reads "FCI 7200" and "AEU." All V5 versions below V5.2-008 and V6 versions below V6.0.14 are included in the recall.

Hazards

The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.

Reported injuries

FCI has received seven reports of AEUs unexpectedly entering a "sleep" mode. No injuries have been reported.

Remedy

FCI will provide a new software chip set for each FireVac System, at no charge.

Products

NameModelUnits
Audio Evacuation Unit276

Parties

Manufacturer
Fire Control Instruments
Made in
United States
Sold at
To FCI distributors nationwide, from January 1998 through April 11, 2003, for a list price of $825.

Consumer contact

Distributors who do not receive the new software chip set or who have additional questions should contact their customer service representative at (800) 633-1311 between 8 a.m. and 5 p.m. ET, Monday through Friday.

Source: CPSC recall 04507. Inclusion in this database is not legal or medical advice.