CPSC, Notifier Announce Recall for Fire Alarm Panels

04508 · Recalled 2003-10-30 · CPSC page

Recalled CPU and DIA components of Notifier fire alarm control panels
Recalled CPU and DIA components of Notifier fire alarm control panels

Description

The fire alarm control panel includes the central processing unit (CPU-2020 and CPU-2) and Display Interface Assembly (DIA-2020 and DIA-2) components of Notifier model AM2020 and AFP1010 fire alarm control panels with date codes from 0100 to 2003 and firmware version 3.0 and 3.01. The date codes appear on the back outer edge of the PC boards.

Hazards

The AEU can enter a "sleep" mode, where it does not communicate with the system. When this occurs, audible evacuation signals associated with the failed AEU will not operate and building occupants may not be warned of an emergency.

Reported injuries

Notifier has received eight reports of trouble signals alarming. In each case the problem was identified and corrected. No injuries have been reported.

Remedy

Notifier will provide an upgraded CPU firmware set for each AM2020 and AFP1010 panel, at no charge.

Products

NameModelUnits
Fire Alarm Control Panel6,000

Parties

Manufacturer
Notifier
Made in
United States
Sold at
Notifier distributors nationwide, from January 2000 through May 2002. The list price for the CPU, DIA combination for the model AM2020 is about $6, 400, the list price for the CPU, DIA combination for the model AFP1010 is about $3, 370.

Consumer contact

Distributors should contact their Notifier customer service representative at (800) 289-3473 between 8 a.m. and 5 p.m. ET, Monday through Friday to receive the firmware upgrade.