CPSC Recalls

Recalls / 2006-10-31

Weil-McLain Recalls Ultra Series Boilers for Carbon Monoxide Hazard

07020 · Recalled 2006-10-31 · CPSC page

CP# Location on Recalled Gas Boiler
CP# Location on Recalled Gas Boiler

Description

The recall involves Weil-McLain Ultra 80, Ultra 105, Ultra 155, Ultra 230 and Ultra 310 condensing, high-efficient, gas-fired boilers for space heating. The user's manual and installation manual have "Ultra Gas-Fired Water Boiler" on the cover. The boilers are wrapped in a glossy silver/flat black jacket and either stand on the floor or are wall-mounted. The serial numbers range from CP5071716 through CP5327000. When the panel on the front of the boiler is removed, a bar-coded label with the serial number is located on the lower right hand side of the boiler itself. "Weil-McLain" is written on the front panel of the boilers.

Hazards

These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to installers that they are intended for use with LP (propane) gas. If an installer connects one of the boilers to LP gas without installing a propane conversion kit, carbon monoxide (CO) can build up due to incomplete combustion, posing a risk of CO poisoning.

Reported injuries

Weil-McLain is aware of one incident where two consumers reported CO poisoning when the boiler installed in their home was connected to LP gas.

Remedy

Consumers who had a Weil-McLain Ultra series boiler installed for use with propane and have not already been contacted by their installer should contact the installer or a heating professional for a free safety inspection. If the boiler was not installed with a propane conversion kit, one will be installed at the time of the inspection at no charge. Heating professionals may contact Weil McLain Technical Service at (219) 879-6561 for more information.

Products

NameModelUnits
Weil-McLain Ultra Series Gas BoilersAbout 16,000

Parties

Manufacturer
Weil-McLain
Made in
United States
Sold at
Plumbing, heating wholesale distributors to plumbers, contractors nationwide, 000, 000.

Consumer contact

For more information, call Weil-McLain toll-free at (866) 426-6172 between 8 a.m. and 4 p.m. CT Monday through Friday, or visit the firm's Web site at www.weil-mclain.com

More images

Recalled Gas Boiler
Recalled Gas Boiler
Wall-monunted Recalled Gas Boiler
Wall-monunted Recalled Gas Boiler

Source: CPSC recall 07020. Inclusion in this database is not legal or medical advice.