CPSC Recalls

Recalls / 2011-02-08

Simplex Fire Alarm Control Panels Recalled by Tyco Safety Products Westminster Due to Failure to Alert Monitoring Centers

11721 · Recalled 2011-02-08 · CPSC page

Description

The recalled fire alarm panel is the Simplex 4100U-NXP panel configured for third party monitoring and running software revision 14.01. The words "Simplex," "4100U" and "Fire Control" appear on the fire alarm's front panel. The software revision number can be identified by pressing the "Menu" key on the panel keypad, selecting "Show Software Revision Level" and pressing "Enter."

Hazards

The recalled fire alarm control panels can fail to send a signal to alert monitoring centers in the event of a fire.

Reported injuries

The firm has received 2 reports of alarms failing to alert monitoring centers. No injuries have been reported.

Remedy

Building managers should contact SimplexGrinnell for a free software upgrade. SimplexGrinnell is contacting its customers directly.

Products

NameModelUnits
Simplex Fire Alarm Control PanelAbout 540

Parties

Manufacturer
Tyco Safety Products Westminster
Made in
United States
Sold at
Distributed by SimplexGrinnell, 000, $20, 000.

Consumer contact

For more information, contact SimplexGrinnell toll-free at (866) 565-6322 or at the firm's website at www.simplexgrinnell.com