CPSC Recalls

Recalls / 2012-04-24

Gems Sensors Recalls Pressure Transducers Used in Fire Pump Controllers Due to Risk of Failure in a Fire

12156 · Recalled 2012-04-24 · CPSC page

Gems 3100 Pressure Transducer
Gems 3100 Pressure Transducer

Description

The Gems 3100 Pressure Transducer is used to detect pressure in a range of applications, including the detection of water pressure as part of a fire pump controller in a fire suppression sprinkler system. The transducer has "Gems Sensors & Controls," as well as the 18-digit part number, printed on a label affixed to the center of the transducer. Part numbers beginning with "3100" are included in this recall.

Hazards

The transducer can fail to accurately detect water pressure in a fire suppression sprinkler system. This could cause the sprinkler system to fail to activate and pump water to the sprinklers in the event of a fire.

Reported injuries

None.

Remedy

Contact Gems to receive enhanced twice monthly inspection instructions and information about a free replacement transducer, when warranted. End-users who use the 3100 Pressure Transducer in other applications in which water pressure is measured should contact Gems to determine if their units are affected.

Products

NameModelUnits
Gems 3100 Pressure Detectors/TransducersAbout 25,000

Parties

Importer
Gems Sensors Inc., of Plainville, Conn.
Made in
England
Sold at
Gems sold the recalled 3100 Pressure Transducers directly to end-users, through distributors

Consumer contact

For additional information, call the company toll-free at (855) 877-9666, between 8 a.m. and 4:30 p.m. ET, Monday through Friday, or visit the firm's website at http://www.gemssensors.com

Source: CPSC recall 12156. Inclusion in this database is not legal or medical advice.