Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard

12721 · Recalled 2012-02-15 · CPSC page

Recalled Bosch fire control panel
Recalled Bosch fire control panel

Description

The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings.

Hazards

On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.

Reported injuries

None reported.

Remedy

All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.

Products

NameModelUnits
Fire Alarm Control PanelAbout 330

Parties

Manufacturer
Bosch Security Systems, Inc.
Made in
China
Sold at
Authorized distributors, installers nationwide, 200.

Consumer contact

For more information, contact Bosch Security Systems at (800) 289-0096 between 8:00 a.m. and 8:00 p.m. ET or visit service/customer care on the firm's website at http://www.boschsecurity.us/en-us/ for instructions on how to download software to update the control panels or otherwise address the problems.

Source: CPSC recall 12721. Inclusion in this database is not legal or medical advice.