Recalls / 2014-11-20
Tyco Fire Protection Recalls Simplex Fire Alarm Control Panels Due to Failure to Activate (Recall Alert)
15709 · Recalled 2014-11-20 · CPSC page

Description
The recalled Simplex 4100ES Fire Control Panel is an addressable fire alarm control panel that can support up to 2,500 addressable points, fire alarm and emergency voice communications and peer-to-peer networking operations. The metal cabinets containing the panel are red or white and measure about 22 inches to 56 inches in height, 24 inches in width and 7 inches in depth. The panels have Simplex 4100ES printed on the front of the panel.
Hazards
A defective chip in the alarm panel can cause premature battery failure and prevent activation of devices during alarm conditions, posing a risk of injury and property damage.
Reported injuries
None reported.
Remedy
SimplexGrinnell is inspecting and replacing all circuit boards with the defective chip. SimplexGrinnell and Tyco are contacting purchasers directly.
Products
| Name | Model | Units |
|---|---|---|
| Simplex 4100ES Fire Alarm Control Panel | About 750 |
Parties
- Manufacturer
- Tyco International de Mexico, S. de R.L. de C.V.
- Importer
- SimplexGrinnell, of Boca Raton, Fla.
- Made in
- Mexico
- Sold at
- SimplexGrinnell, 000.
Consumer contact
Tyco at (800) 746-7539 from 8:30 a.m. to 4:30 p.m. ET Monday through Friday or online at www.tycosimplexgrinnell.com and click on the Recall Alert button.