Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO

16134 · Recalled 2016-03-31 · CPSC page

Fire Alarm Panel
Fire Alarm Panel

Description

This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

Hazards

When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.

Reported injuries

No incidents or injuries have been reported.

Remedy

Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.

Products

NameModelUnits
Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)About 1,000

Parties

Distributor
Gamewell-FCI of Northford, Conn.
Made in
United States
Sold at
Authorized distributors

Consumer contact

Gamewell-FCI at 800-274-4324 from 7 a.m. to 7 p.m. ET Monday through Friday or online at www.gamewell-fci.com and click on "Safety Recall" for more information.