Carrier® Recalls to Repair Commercial Rooftop HVAC Units Due to Fire Hazard (Recall Alert)

18731 · Recalled 2018-03-19 · CPSC page

40/50 series LC rooftop HVAC unit
40/50 series LC rooftop HVAC unit

Description

This recall involves Carrier WeatherExpert 6-23 ton, 48/50 series, light commercial rooftop HVAC units intended for use in commercial and institutional buildings and that have a factory installed dehumidification feature. The model numbers are 48/50LC07-26 with an A in the 6th digit and a 0 (zero) in the 14th digit of the model number (e.g., 48LCTA24F2M5-0S1B3). Note that dashes should be counted as digits in the model number. The serial numbers are 1214P to 3317P. The model and serial number can be found on the unit rating plate located on the back of the unit.

Hazards

The HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard.

Reported injuries

Carrier has received one report of a fan not shutting off during installation testing. No injuries have been reported.

Remedy

Purchasers should immediately contact their Carrier dealer for a free repair, which consists of free replacement and installation of the electronic control board. The firm is contacting all known purchasers.

Products

NameModelUnits
Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer optionAbout 530

Parties

Manufacturer
Carrier México, S.A. de C.V.
Importer
Carrier Corporation, of Jupiter, Fla.
Made in
Mexico
Sold at
Carrier distributors nationwide, 000, $93, 000.